Integrated temperature transmitter TM110

Principle and Characteristics

TM110 contains a PT100 probe, PT100 resistance value will change with temperature, ST40 internal circuit to convert its value into linear analog output. Simple installation, multiple ranges, multiple sizes of probes, full stainless steel housing, compact and strong structure. And optional field instrument and cabinet type control table.

product application

It can be used in water supply system, hydraulic system, pneumatic system, cooling system, heating system, air condi- tioning system, automation engineering, etc.

Technical parameters

  • Measuring range: The custom
  • Linearity: < 0.1%
  • Accuracy: ±0.2 K + 0.2% of full scale
  • Resolution: 0.1 K
  • Cardiac compression: Ф 6 type probe and 40 bar, Ф 8 probe 100 bar
  • Influence of temperature: 0.1 K / 10 K
  • Response time:T90 / t-50, 2.3 seconds, 5.4 seconds
  • Working Voltage: 12... 30 VDC
  • Electrical Protection: Reverse pole, overload protection
  • Sensors: PT100
  • Ambient temperature: -25... 80 c
  • Level of protection: IP65
  • Shell materials: Stainless steel
  • Material of contact liquid part: Stainless steel 1.4571
  • Electrical connenction: Terminal connection
Dimension Image 2 Dimension Image 2

Size Chart (mm)

Dimension Image 2
TM110- C2080 A 6 25 G14M - - - Detailed
TM110- Integrated temperature transmitter
C2080 Range -20...80℃ (user can specify range)
C0100 Range 0...100℃ (user can specify range)
C50200 Range -50...200℃ high and low temperature type (user can specify range)
C50400 Range -50...400℃ high and low temperature type (user can specify range)
C100100 Range -100...100℃ high and low temperature type (user can specify range)
C200100 Range -200...100℃ high and low temperature type (user can specify range)
A Analog range output: 4...20mA
V05 Analog range output: 0...5V
V15 Analog range output: 1...5V
V010 Analog range output: 0...10V
V110 Analog range output: 1...10V
/6 Pipe diameter Φ6
/8 Pipe diameter Φ8
/25 Probe length L 25mm
/50 Probe length L 50mm
/75 Probe length L 75mm
/100 Probe length L 100mm
G14M Thread interface G1/4 external thread
G12M Thread interface G1/2 external thread
H50 Health chuck 50.5
- No cold end (Measuring range: ≤ -20~100℃)
L30 Cold end 30MM (Measuring range: ≤ -50~150℃)
L50 Cold end 50MM (Measuring range: ≤ -100~250℃)
L100 Cold end 100MM (Measuring range: ≤ -200~400℃)
- Hersman plug (default)
M M12 aviation plug
- No display
D10A With LED display (only for 4~20mA current output signal type)

Note: Temperature probe plus protective sleeve selection thread G1/2, thread smaller than G1/2 does not support probe rod sheath.

Dimension Image 2

Integrated display unit

The display table is an electronic device used for digital display of the sensor signal, which can be set to the required display range by setting the button

  • Free programming via processor
  • No field setup required
  • With 4... Sensor with 20mA output
  • Protection level IP55
  • Easy to operate
Dimension Image 2 Dimension Image 2 Dimension Image 2